Venting a atmospheric gas water heater with a 15 ft run
| Vent material | Type B double-wall vent, or a lined masonry chimney |
|---|---|
| Vent size | 3″ or 4″ |
| Length limithorizontal run may not exceed 75% of the vertical height | set by rise, not by length |
| Vertical rise neededfor 15 ft of horizontal run | 20ft |
| Vent run | 15ft |
| Combustion air | drawn from the room — a closed closet needs two vents, each 1 in² per 1,000 BTU/hr |
| Heater typethe ordinary gas heater with a draft hood on top | atmospheric gas (Category I) |
Notes
- "Can I vent it with PVC" depends entirely on the category, and getting it wrong is not a code technicality. atmospheric gas (Category I) vents with Type B double-wall vent, or a lined masonry chimney. Plastic on a Category I heater softens and fails at exhaust temperatures it was never rated for; metal on a condensing heater is eaten by acidic condensate within a few years. The appliance's own manual overrides every general rule, including this page.
- A Category I vent runs on buoyancy, so height is the constraint, not length. 15 ft of horizontal needs at least 20 ft of vertical above it, every horizontal section must rise at least ¼ inch per foot, and the whole thing has to terminate above the roofline with the right clearance. A vent that runs level, or that drops even slightly, spills exhaust into the room.
- Combustion air is the part that gets skipped. drawn from the room — a closed closet needs two vents, each 1 in² per 1,000 BTU/hr. A confined space — a closet, a small utility room — needs either 50 ft³ of volume per 1,000 BTU/hr or two permanent openings, one high and one low, each 1 in² per 1,000 BTU/hr. Sealing up a draughty basement is a common way to make a heater that worked for twenty years start backdrafting.
- A drain pan with a line to somewhere is worth its cost the first time. Tanks fail by leaking, not by bursting, and they do it while nobody is home. Where the heater sits above finished space, most codes now require the pan and the drain; where they do not, install it anyway.
- Have the draft checked after any change to the house. A new bathroom fan, a kitchen hood, or a tighter set of windows can pull enough air to reverse a Category I vent. A smoke test at the draft hood takes a minute and is the difference between a working flue and carbon monoxide in the hallway.
Type B double-wall vent, or a lined masonry chimney
That is the material a atmospheric gas water heater vents with, at 3″ or 4″. Getting it wrong is not a paperwork problem: plastic on a hot-exhaust appliance softens and fails, and metal on a condensing appliance is eaten through by acidic condensate.
Combustion air
drawn from the room — a closed closet needs two vents, each 1 in² per 1,000 BTU/hr
A confined space needs either 50 ft³ of volume per 1,000 BTU/hr, or two permanent openings — one high, one low — each sized at 1 in² per 1,000 BTU/hr. Sealing up a draughty basement is a well-documented way to make a heater that vented correctly for twenty years start spilling exhaust into the room.
Where the manual beats every general rule
Vent length limits, permitted materials and termination clearances are specific to the model. This page tells you which family of answers to expect; the appliance's installation manual is the authority, and the inspector will read it rather than this.
Nearby sizes
- Venting a power-vent gas water heater with a 15 ft run
- Venting a direct-vent gas water heater with a 15 ft run
- Venting a atmospheric gas water heater with a 10 ft run
- Venting a atmospheric gas water heater with a 20 ft run
- Venting a atmospheric gas water heater with a 5 ft run
- Venting a atmospheric gas water heater with a 30 ft run
Read more
- T&P Valve Keeps Releasing Water — Thermal Expansion, Not a Bad ValveThe valve is the messenger. Replacing it silences the message for a few weeks and leaves the pressure exactly where it was.
- Water Heater Replacement Cost by State — 50 Gallon Gas, All 51Like-for-like is the cheap path. Every change away from it adds a trade, and that is why two quotes on "a new water heater" can differ by three thousand dollars.
- Why Hot Water Runs Out Faster in Winter (And It Is Not a Fault)Nothing broke in October. The water arriving from the street got colder, and that changes both how much hot water you have and how fast it comes back.
- Is a 40 Gallon Water Heater Enough for 2 Bathrooms?Two bathrooms is not a load. Two showers at 7:10am is a load, and the answer changes completely depending on what heats the water.